AMPLIFIER AIDED CURRENT TRANSFORMER
MODEL CT2001

Specifications at 25 degrees C:
Current Ratio  2000:1 Amperes
Transformation Accuracy 0.01% + 0.001% of full scale
Full Scale Input Current  2000 Amperes
Primary Burden  Resistance of Primary Circuit
Absolute Maximum Input  3000 Amperes
Maximum Secondary Current  1.1 Ampere
Maximum Secondary Voltage
         @ 1 ohm burden  1.1 volts
         @ 4 ohms or greater 2 volts
Frequency Range 40 – 1000 Hz.
Phase Shift  Less than 0.006 degrees
Distortion Less than 0.1%
AC Calibration Cycle  None Required
AC Temperature Coefficient  5 ppm/degree C
DC Offset  Less than 10 microamperes
DC Temperature Coefficient 10 ppm
DC Calibration Cycle  3 Months
Operating Temperature  0 – 40 degrees C
Relative Humidity  5 – 90% non condensing
Power Consumption  50 VA’s maximum
Power Requirement – as marked  115 or 230 V 50/60 Hz. +/-10% 
Weight  6 pounds
Physical Size
    Amplifier  7”x3”x5” WxHtxD (Enclosure only)
    Sense Transformer 4.0"I.D.x7.87"O.D.x1.5"Ht.
    Connecting Cable  24 inches

JAMB Industries

Boonton, NJ 07005-9105 USA
Voice/FAX 973-263-9295
email: abudgin@optonline.net

05/17